Article 110 Requirements for Electrical Installations
I. General
110.1 |
Scope |
110.2 |
Approval |
Only approved equipment and conductors are acceptable.
110.3 |
Examination, Identification, Installation, and Use of Equipment |
The Code lists considerations for the examination of equipment such as mechanical strength, electrical insulation, etc.
110.4 |
Voltages |
110.5 |
Conductors |
Copper is to be used unless otherwise specified. Sizes given are for copper unless otherwise specified.
110.6 |
Conductor SizesExpressed in American Wire Gage (AWG) or in Circular Mils |
110.7 |
Insulation Integrity |
110.8 |
Wiring Methods |
110.9 |
Interrupting Rating |
110.10 |
Circuit Impedance and Other Characteristics |
The entire electrical circuit, including all devices and wire, must be chosen and coordinated so that a fault will be cleared before extensive damage takes place.
110.11 |
Deteriorating Agents |
110.12 |
Mechanical Execution of Work |
110.13 |
Mounting and Cooling of Equipment |
110.14 |
Electrical Connections |
110.15 |
High-Leg Marking |
110.16 |
Flash Protection |
110.18 |
Arcing Parts |
110.19 |
Light and Power from Railway Conductors |
110.21 |
Marking |
110.22 |
Identification of Disconnecting Means |
110.23 |
Current Transformers |
II. 600 Volts, Nominal, or Less
110.26 |
Spaces about Electrical Equipment |
(A) Clearances for three conditions are noted. Condition 1 consists of live exposed parts on one side and no live or grounded parts on the other side of the working space or guarded live parts (wood or other insulating material used) on both sides of the working space. Condition 2 consists of exposed live parts on one side and grounded parts on the other side. Condition 3 consists of exposed live parts on both sides. For voltages to ground between 0 and 150 V, a minimum clear distance of 900 mm (3 ft.) is required in all cases. For voltages to ground between 151 and 600 V, Condition 1 requires 900 mm (3 ft.) clearance. Condition 2 requires 1.1 m (3½ ft.), and Condition 3 requires 1.2 m (4 ft.). No working space is required behind assemblies where no renewable parts are on the back and all wiring is accessible from the front (such as panelboards). A minimum of 762 mm (30 in.) in width is required in front of electrical equipment as well as room for a 90° opening of doors. There are requirements in the Code when the voltage is not greater than 30 volts rms, 42 volts peak, or 60 volts dc. There are also requirements in existing buildings where equipment is being replaced.
(E) Headroom of 2 m (6½ ft.) is required above service equipment, motor control centers, panelboards, or switchboards, with the exception of dwelling units not in excess of 200 A. If the equipment exceeds 2 m (6½ ft.), headroom shall be at least the height of the equipment.
110.27 |
Guarding Live Parts |
III. Over 600 Volts, Nominal
110.30 |
General |
110.31 |
Enclosure for Electrical Installations |
110.32 |
Work Space about Equipment |
110.33 |
Entrance and Access to Work Space |
110.34 |
Work Space and Guarding |
110.36 |
Circuit Conductors |
110.40 |
Temperature Limitations at Terminations |
IV. Tunnel Installations Over 600 Volts, Nominal
110.51 |
General |
110.52 |
Overcurrent Protection |
110.53 |
Conductors |
110.54 |
Bonding and Equipment Grounding Conductors |
110.55 |
Transformers, Switches, and Electrical Equipment |
110.56 |
Energized Parts |
110.57 |
Ventilation System Controls |
110.58 |
Disconnecting Means |
110.59 |
Enclosures |
V. Manholes and Other Electric Enclosures Intended for Personnel, All Voltages
110.70 |
General |
110.71 |
Strength |
110.72 |
Cabling Work Space |
110.73 |
Equipment Work Space |
110.74 |
Bending Space for Conductors |
110.75 |
Access to Manholes |
110.76 |
Access to Vaults and Tunnels |
110.77 |
Ventilation |
110.78 |
Guarding |
110.79 |
Fixed Ladders |