Article 400: Flexible Cords and Cables
Article 400 Flexible Cords and Cables
I. General
400.1 |
Scope |
400.2 |
Other Articles |
400.3 |
Suitability |
400.4 |
Types |
Table 400.4 lists the approved types of flexible cables and cords. A cable or cord not on this list must have a special investigation. Notes to the table should be reviewed.
400.5 |
Ampacity of Flexible Cords and Cables |
Tables 405.5(A) and 405.5(B) show the ampacity of flexible cords or cables of up to three current-carrying conductors. When more than three current-carrying conductors are used, a derating factor is used. These derating factors are shown in a table in the code. There is information on Ultimate Insulation Temperature. There are additional requirements. If the cords are used in an environment where the ambient temperature is higher than 30°C (86°F), then the temperature correction factors from Table 310.16 are applied to the ampacity allowed in Table 400.5.
400.6 |
Marking |
400.7 |
Uses Permitted |
(1) Pendants; (2) wiring of luminaires (fixtures); (3) connection of portable lamps or appliances; (4) for elevator cables; (5) cranes and hoists; (6) for utilization equipment if they are to be moved a lot; (7) to prevent noise and vibration transmission; (8) where removal for maintenance is required and the appliance is to use a flexible cord or cable; (9) connection of moving parts; (10) where specifically permitted in the code. When used as indicated in (3), (6), and (8), a plug must be used on the cord and it must be plugged into a receptacle for power. There is an exception in 368.56: there are requirements for attachment plugs and multioutlet assemblies.
400.8 |
Uses Not Permitted |
Unless permitted in Section 400.7, they are not permitted: (1) for a substitute for fixed wiring of a building; (2) installed through a hole in walls, ceilings, or floors; (3) through doorways, windows, or similar openings; (4) installed concealed (there is an exception in 368); (5) attached to building surfaces; (6) installed in raceways unless permitted by the code; (7) where subject to physical damage.
400.9 |
Splices |
400.10 |
Pull at Joints and Terminals |
Some type of strain relief must be provided (i.e., a knot, tape, or special fitting).
400.11 |
In Show Windows and Show Cases |
Use only Type S, SO, SE, SEO, SEOO, SOO, SJ, SJE, SJO, SJEO, SJEOO, SJOO, ST, STO, STOO, SJT, SJTO, SJTOO, SEW, SEOW, SEOOW, SJEW, SJEOW, SJEOOW, SJOW, SJTOW, SJTW, SJOOW, SOW, SOOW, SJTOOW, STW, STOW, or STOOW. This restriction is not necessary for chain-supported lighting fixtures or portable lamps and display merchandise.
400.12 |
Minimum Size |
Refer to Table 400.4.
400.13 |
Overcurrent Protection |
If not smaller than 18 AWG or tinsel cords or a cord approved for a specific appliance, no separate overcurrent protection is required. They are protected in accordance with 240.4.
400.14 |
Protection from Damage |
II. Construction Specifications
400.20 |
Labels |
400.21 |
Nominal Insulation Thickness |
Refer to Table 400.4.
400.22 |
Grounded-Conductor Identification |
One conductor that is used as a grounded circuit conductor must be clearly marked. Identification methods include (1) a white or gray braid, (2) a tracer of a distinguishable color in the braid, (3) white or gray insulation, (4) white or gray separator, (5) tinned conductor, and (6) some distinguishable surface marking.
400.23 |
Equipment Grounding-Conductor Identification |
This conductor must also have a distinguishing marking of a colored braid, colored insulation, or colored cover. The color to be used is either green or green with yellow stripes.
400.24 |
Attachment Plugs |
III. Portable Cables Over 600 Volts, Nominal
400.30 |
Scope |
400.31 |
Construction |
400.32 |
Shielding |
400.33 |
Grounding |
400.34 |
Minimum Bending Radii |
400.35 |
Fittings |
400.36 |
Splices and Terminations |