Example No. D1(a) One-Family Dwelling
The dwelling has a floor area of 1500 square feet exclusive of an unfinished cellar not adaptable for future use, unfinished attic, and open porches. Appliances are a 12-kW range and a 5.5-kW, 240-volt dryer. Assume range and dryer kW ratings equivalent to kVA ratings in accordance with Sections 220.54 and 220.55.
Calculated Load [See 220.40]
General lighting load: 1500 sq. ft. at 3 volt-amperes per sq. ft. = 4500 volt-amperes.
Minimum Number of Branch Circuits Required [See Sec-tion 210.11(A)]
General lighting load: 4500 volt-amperes ÷ 120 V = 37.5 A. This requires three 15-A, 2-wire or two 20-A, 2-wire circuits.
Small appliance load: two 2-wire, 20-A circuits [see 210.11(C)(1)].
Laundry load: one 2-wire 20-A circuit [see 210.11(C)(2)].
Bathroom branch circuit: One 2-wire, 20-A circuit (no additional calculation is required for this circuit) [see 210.11(C)(3)].
Minimum Size Feeder Required [See 220.40]
|
General lighting |
4500 VA |
|
Small appliance |
3000 VA |
|
Laundry |
1500 VA |
|
Total general light and small appliance |
9000 VA |
|
3000 volt-amperes at 100% |
3000 VA |
|
9000 VA - 3000 VA = 6000 volt-amperes at 35% |
2100 VA |
|
Net load |
5100 VA |
|
Range (see Table 220.55) |
8000 VA |
|
Dryer load (see Table 220.54) |
5500 VA |
|
Net calculated load |
18,600 VA |
Net calculated load for 120/240-volt 3-wire single-phase service or feeder
Sections 230.42(B) and 230.79 require service conductors and disconnecting means rated not less than 100 amperes.
Calculation for Neutral for Feeder and Service
|
Lighting and small appliance load |
5100 VA |
|
Range: 8000 volt-amperes at 70% (see 220.61) |
5600 VA |
|
Dryer: 5500 volt-amperes at 70% (see 220.61) |
3850 VA |
|
Total |
14,550 VA |
Calculated Load for Neutral