Example No. D1(b) One-Family Dwelling

Assume same conditions as Example No. D1(a), plus addition of one 6-ampere, 230-volt room air-conditioning unit and one 12-ampere, 115-volt room air-conditioning unit,* one 8-ampere, 115-volt rated waste disposer, and one 10-ampere, 120-volt rated dishwasher. See Article 430 for general motors and Article 440, Part VII, for air-conditioning equipment. Motors have nameplate ratings of 115 V and 230 V for use on 120-V and 240-V nominal voltage systems.

From Example No. D1(a), feeder current is 78 amperes (3-wire 240 volts).

 

Line A

Neutral

Line B

Amperes from Example No. D1(a)

78

61

78

One 230-V air conditioner

6

6

One 115-V air conditioner and 120-V dishwasher

12

12

10

One 115-V disposal

8

8

25% of largest motor (see 430.24)

3

2

2

Total amperes per line

99

83

104

Therefore, the service would be rated 110 A.

*(For feeder neutral, use largest of the two appliances for unbalance.)